Professional interlocked armored cable manufacturer from China, Meet your kinds of requirement of AC90, ACWU90, Teck 90 Control Cable, Teck 90 EPR/XPLE Cable, Aluminum Alloy Interlocked Armor(AIA) Cable. With over 30 years of production experience and 15 years of export experience, factory price without any third party.
The cable size can be customized according to your requirement, On-time delivery.
1KV/5KV Teck 90 Cable 1,3 Core XLPE/EPR/PVC Insulated MC Power Cable;600v Interlocked MC XLPE Armoured Cable – AC/ ACWU90 / HL-XHHW-2 Cable
- Get a quote by email: supplier@huadongcablegroup.com
Teck 90 1/C Cu 1KV XLPE/EPR/PVC Insulated MC Power Cable
- Voltage: 1kV
- Conductor: Class B stranded copper
Size(AWG/MCM): 1,2,4,6,8,1/0,2/0,4/0AWG Or 250, 300,350,500,750 MCM
Insulation: XLPE
Grounding Conductors: Uninsulated Class B stranded grounding conductor
Assembly: Multiple conductor with suitable fillers and a binder tape
Colour Code:
– 2/C black, white
– 3/C red, black, blue
– 4/C red, black, blue, white
– For cables larger than No. 2 AWG or more than 4/C, the insulation is black and numbered
Inner Jacket: Polyvinyl Chloride (PVC) Armour; Aluminum Interlocked Armour (AIA)
Overall Jacket: Black PVC (optional colors available)
Teck 90 3/C Cu 1KV XLPE/PVC AIA PVC-NS
- Voltage: 1kV
- Conductor: Class B stranded copper compressed or compact in accordance with ASTM B3 and ASTM B8
Insulation: XLPE (Cross Linked Polyethylene)
Minimum Average Thickness: 250 kcmil to 1000 kcmil – 0.090 inches (2.3 mm)
Inner Jacket:
1. Black PVC
2.Thickness – 250 kcmil to 1000 kcmil = 0.060″ (1.5 mm)- minimum average
Armour: Aluminum Interlocked Armour (AIA)
Overall Jacket:
Black PVC (optional colours available)
Minimum Thickness
– 250 kcmil to 400 kcmil = 0.050 inches (1.3 mm)
Teck 90 5KV 1 Core Non shielded-TR-XLPE Cable
- Voltage: 5 kV
- Conductor:
1. Class B stranded copper – compressed or compact
– in accordance with ASTM B3 and ASTM B8
2. Optional Class B compact stranded 8000 Series Aluminum ACM
Insulation
1.TR-XLPE (tree retardant cross linked polyethylene
2. Thickness: 0.090 inches (2.3 mm) – nomina
3. Insulation Level: 100% – ungrounded system
4. Temperature Rating: 90°C
Conductor Shield: Extruded semi-conducting thermosetting polymeric layer
Concentric Bonding Conductors
-Class B – concentric bare copper wire serve
Inner Jacket: Black PVC Jacket thickness:
2 AWG to No. 1/0 AWG = 0.045”(1.2 mm)
2/0 AWG to 1000 kcmil = 0.060”(1.6 mm)
Armour: -Aluminum Interlocked Armour (AIA)/Optional Galvanized Steel Interlocked Armour (GSIA)
Overall Jacket: Orange PVC (optional colours available)
-Thickness:
1. 2 AWG to 400 kcmil = 0.045”(1.2 mm)
2. 500 kcmil to 1000 kcmil = 0.055”(1.4 mm)
Teck 90 5KV 3 Core Non-Shielded EPR/XLPE Cable
- Voltage: 5kV
- Conductor
1. Class B stranded copper, compressed or compact, in accordance with ASTM B3 and ASTM B8
2. Optional Class B compact stranded 8000 Series Aluminum ACMConductor Shield
1. Extruded semi-conducting thermosetting polymeric layerGrounding Conductor
1. Class B compressed or compact stranded bare copper
Insulation
1. No-Lead EPR (ethylene propylene rubber)
2. Thickness: 0.090” (2.3 mm) – nominal
3. 90°C rated
Inner Jacket
1. Black PVC
2. Thickness:
– No. 2 AWG to No. 3/0 AWG = 0.080” (2.0 mm)
– No. 4/0 AWG to 500 kcmil = 0.110” (2.8 mm)
– 750 kcmil to 1000 kcmil = 0.140” (3.6 mm)
Armour
1. Aluminum Interlocked Armour (AIA)
2. Optional Galvanized Steel Interlocked Armour (GSIA)
Overall Jacket
1. Orange PVC (optional colours available
2. Thickness:
– No. 2 AWG to 250 kcmil = 0.060” (1.5 mm)
– 350 kcmil to 750 kcmil = 0.075” (1.9 mm)
– 1000 kcmil = 0.090” (2.3 mm)
Aluminum 600V Armored MC Cable Three or Four Conductor UL Type MC, Aluminum Conductor, XHHW-2, AIA, 90°C Dry, Rated 600 V
- Voltage: 0.6/1kV
- Conductor: Annealed compact stranded AA-8000 series Aluminum Conductor Material (ACM).
Insulation: Abrasion, moisture, and heat resistant black crosslinked polyethylene (XLPE) with colored stripe.
Assembly: Cabled assembly with an equipment grounding conductor and a binder tape overall.
Armor: Aluminum Interlocked Armor (AIA). - CONDUCTOR IDENTIFICATION
Three Conductors: Black, Black with Red Stripe, Black with White Stripe
Four Conductors: Black, Black with Red Stripe, Black with Blue Stripe, Black with White Stripe - APPLICATIONS
UL Type MC cables with XHHW-2 conductors are primarily used for services, feeders and branch circuits in commercial and residential applications in accordance with the NEC. Suitable applications include for indoor power and lighting circuits, exposed or concealed, cable tray, raceway (conduit) and embedded in plaster or in contact with masonry. The cable is suitable for dry locations only at temperatures not to exceed 90°C. The cable is rated 600 V. - STANDARDS
ASTM B800 — 8000 Series Aluminum Alloy Wire for Electrical Purposes – Annealed and Intermediate Tempers
ASTM B801 — Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy for Subsequent Covering or Insulation
UL 44 — Thermoset-Insulated Wires and Cables
UL 1479 — Fire Tests of Through-Penetration Firestops
UL 1569 — Metal-Clad Cables.
ICEA S-95-658 / NEMA WC70 — Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
Federal Specification J-C-30B
Aluminum 600V Armored MC Cable Three or Four Conductor UL Type MC, Aluminum Conductor THHN/THWN-2, AIA, 90°C Dry, Rated 600 V
- Voltage: 0.6/1kV or 2kV
- CONSTRUCTION
Conductor: Annealed compact stranded AA-8000 series Aluminum Conductor Material (ACM).
Insulation: Low coefficient of friction, abrasion, moisture, and heat resistant colored polyvinyl chloride (PVC).
Covering: Low coefficient of friction, abrasion, moisture, and heat resistant translucent Nylon polyamide.
Assembly: Cabled assembly with an equipment grounding conductor and a binder tape overall.
Armor: Aluminum Interlocked Armor (AIA). - CONDUCTOR IDENTIFICATION
Three Conductors: Black, Black with Red Stripe, Black with White Stripe
Four Conductors: Black, Black with Red Stripe, Black with Blue Stripe, Black with White Stripe - APPLICATIONS
UL Type MC cables with THHN/THWN-2 conductors are primarily used for services, feeders and branch circuits in commercial and residential applications in accordance with the NEC. Suitable applications include for indoor power and lighting circuits, exposed or concealed, cable tray, raceway (conduit) and embedded in plaster or in contact with masonry. The cable is suitable for dry locations only at temperatures not to exceed 90°C. The cable is rated 600 V. - STANDARDS:
ASTM B800 — 8000 Series Aluminum Alloy Wire for Electrical Purposes – Annealed and Intermediate Tempers
ASTM B801 — Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy for Subsequent Covering or Insulation
UL 83 — Thermoplastic-Insulated Wires and Cables
UL 1479 — Fire Tests of Through-Penetration Firestops
UL 1569 — Metal-Clad Cables.
ICEA S-95-658 / NEMA WC70 — Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
Federal Specification J-C-30B
Armored 5kV/8kv/15kv/35kv 100% or 133% CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket
- Get a quote by email: supplier@huadongcablegroup.com
Armored 5kV 100% or 133% CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket
- Voltage: 5kV
- Construction
Conductor: Class A or B Compressed concentric stranded copper conductor. Optional water-blocking.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation
Insulation: Extruded, unfilled Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: The metallic shield is flat uncoated 5-mil thick copper tape helically applied with minimum 20% overlap
Ground Wire: Three bare copper ground wires placed at the interstice of the conductor.
Fillers: Non hygroscopic fillers, forming a firm and cylindrical cable core.
Binder Tape: A binder tape is applied to maintain core symmetry and mechanical stability.
Armor: Aluminum Interlocked Armor applied over the binder tape of the cable core
Jacket: Black, sunlight resistant, flame retardant PVC jacket - Standards:
ICEA S-93-639, 5-46 kV Shielded Power Cable
ICEA S-97-682, Utility Shielded Power Cable Rated 5-46 kV
UL-1072 MV-105
UL-1569, Metal Clad Cables
IEEE 383 Flame Test
For 105°C continuous, 140°C emergency, 250°C short-circuit operation.
UL MC-HL available upon request
Armored 8kV 100% or 133% CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket
- Voltage: 8kV
- Construction
Conductor: Class A or B Compressed concentric stranded copper conductor. Optional water-blocking.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation
Insulation: Extruded, unfilled Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: The metallic shield is flat uncoated 5-mil thick copper tape helically applied with minimum 20% overlap
Ground Wire: Three bare copper ground wires placed at the interstice of the conductor.
Fillers: Non hygroscopic fillers, forming a firm and cylindrical cable core.
Binder Tape: A binder tape is applied to maintain core symmetry and mechanical stability.
Armor: Aluminum Interlocked Armor applied over the binder tape of the cable core
Jacket: Black, sunlight resistant, flame retardant PVC jacket
Standards
ICEA S-93-639, 5-46 kV Shielded Power Cable
ICEA S-97-682, Utility Shielded Power Cable Rated 5-46 kV
UL-1072 MV-105
UL-1569, Metal Clad Cables
IEEE 383 Flame Test
For 105°C continuous, 140°C emergency, 250°C short-circuit operation.
UL MC-HL available upon request
Armored 15kV 100% or 133% CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket
- Voltage: 15kV
- Construction
Conductor: Class A or B Compressed concentric stranded copper conductor. Optional water-blocking.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation
Insulation: Extruded, unfilled Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: The metallic shield is flat uncoated 5-mil thick copper tape helically applied with minimum 20% overlap
Ground Wire: Three bare copper ground wires placed at the interstice of the conductor.
Fillers: Non hygroscopic fillers, forming a firm and cylindrical cable core.
Binder Tape: A binder tape is applied to maintain core symmetry and mechanical stability.
Armor: Aluminum Interlocked Armor applied over the binder tape of the cable core
Jacket: Black, sunlight resistant, flame retardant PVC jacket
Standards
AEIC CS8, Specifications for Shielded Power Cable, 5-46kV
ICEA S-93-639, 5-46 kV Shielded Power Cable
ICEA S-97-682, Utility Shielded Power Cable Rated 5-46 kV
UL-1072 MV-105
UL-1569, Metal Clad Cables
IEEE 383 Flame Test
For 105°C continuous, 140°C emergency, 250°C short-circuit operation.
UL MC-HL available upon request
Armored 25kV 100% or 133% CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket Cable
- Voltage: 25kV
- Construction
Conductor: Class A or B Compressed concentric stranded copper conductor. Optional water-blocking.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation
Insulation: Extruded, unfilled Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: The metallic shield is flat uncoated 5-mil thick copper tape helically applied with minimum 20% overlap
Ground Wire: Three bare copper ground wires placed at the interstice of the conductor.
Fillers: Non hygroscopic fillers, forming a firm and cylindrical cable core.
Binder Tape: A binder tape is applied to maintain core symmetry and mechanical stability.
Armor: Aluminum Interlocked Armor applied over the binder tape of the cable core
Jacket: Black, sunlight resistant, flame retardant PVC jacket
Standards
AEIC CS8, Specifications for Shielded Power Cable, 5-46kV
ICEA S-93-639, 5-46 kV Shielded Power Cable
ICEA S-97-682, Utility Shielded Power Cable Rated 5-46 kV
UL-1072 MV-105
UL-1569, Metal Clad Cables
IEEE 383 Flame Test
For 105°C continuous, 140°C emergency, 250°C short-circuit operation.
UL MC-HL available upon request
Armored 35kV CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket Cable
- Voltage: 35kV
- Construction
Conductor: Class A or B Compressed concentric stranded copper conductor. Optional water-blocking.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation
Insulation: Extruded, unfilled Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: The metallic shield is flat uncoated 5-mil thick copper tape helically applied with minimum 20% overlap
Ground Wire: Three bare copper ground wires placed at the interstice of the conductor.
Fillers: Non hygroscopic fillers, forming a firm and cylindrical cable core.
Binder Tape: A binder tape is applied to maintain core symmetry and mechanical stability.
Armor: Aluminum Interlocked Armor applied over the binder tape of the cable core
Jacket: Black, sunlight resistant, flame retardant PVC jacket
Standards:
AEIC CS8, Specifications for Shielded Power Cable, 5-46kV
ICEA S-93-639, 5-46 kV Shielded Power Cable
ICEA S-97-682, Utility Shielded Power Cable Rated 5-46 kV
UL-1072 MV-105
UL-1569, Metal Clad Cables
IEEE 383 Flame Test
For 105°C continuous, 140°C emergency, 250°C short-circuit operation.
UL MC-HL available upon request