Professional interlocked armored cable manufacturer from China, Meet your kinds of requirement of AC90, ACWU90, Teck 90 Control Cable, Teck 90 EPR/XPLE Cable, Aluminum Alloy Interlocked Armor(AIA) Cable. With over 30 years of production experience and 15 years of export experience, factory price without any third party. The cable size can be customized according to your requirement, On-time delivery.
1KV/5KV Teck 90 Cable 1,3 Core XLPE/EPR/PVC Insulated MC Power Cable;600v Interlocked MC XLPE Armoured Cable – AC/ ACWU90 / HL-XHHW-2 Cable
Teck 90 1/C Cu 1KV XLPE/EPR/PVC Insulated MC Power Cable
Voltage: 1kV
Conductor: Class B stranded copper
Size(AWG/MCM): 1,2,4,6,8,1/0,2/0,4/0AWG Or 250, 300,350,500,750 MCM
Insulation: XLPE
Grounding Conductors: Uninsulated Class B stranded grounding conductor
Assembly: Multiple conductor with suitable fillers and a binder tape
Colour Code:
– 2/C black, white
– 3/C red, black, blue
– 4/C red, black, blue, white
– For cables larger than No. 2 AWG or more than 4/C, the insulation is black and numbered
Aluminum 600V Armored MC Cable Three or Four Conductor UL Type MC, Aluminum Conductor, XHHW-2, AIA, 90°C Dry, Rated 600 V
Voltage: 0.6/1kV
Conductor: Annealed compact stranded AA-8000 series Aluminum Conductor Material (ACM).
Insulation: Abrasion, moisture, and heat resistant black crosslinked polyethylene (XLPE) with colored stripe.
Assembly: Cabled assembly with an equipment grounding conductor and a binder tape overall.
Armor: Aluminum Interlocked Armor (AIA).
CONDUCTOR IDENTIFICATION
Three Conductors: Black, Black with Red Stripe, Black with White Stripe
Four Conductors: Black, Black with Red Stripe, Black with Blue Stripe, Black with White Stripe
APPLICATIONS
UL Type MC cables with XHHW-2 conductors are primarily used for services, feeders and branch circuits in commercial and residential applications in accordance with the NEC. Suitable applications include for indoor power and lighting circuits, exposed or concealed, cable tray, raceway (conduit) and embedded in plaster or in contact with masonry. The cable is suitable for dry locations only at temperatures not to exceed 90°C. The cable is rated 600 V.
STANDARDS
ASTM B800 — 8000 Series Aluminum Alloy Wire for Electrical Purposes – Annealed and Intermediate Tempers
ASTM B801 — Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy for Subsequent Covering or Insulation
UL 44 — Thermoset-Insulated Wires and Cables
UL 1479 — Fire Tests of Through-Penetration Firestops
UL 1569 — Metal-Clad Cables.
ICEA S-95-658 / NEMA WC70 — Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
Federal Specification J-C-30B
Aluminum 600V Armored MC Cable Three or Four Conductor UL Type MC, Aluminum Conductor THHN/THWN-2, AIA, 90°C Dry, Rated 600 V
Voltage: 0.6/1kV or 2kV
CONSTRUCTION
Conductor: Annealed compact stranded AA-8000 series Aluminum Conductor Material (ACM).
Insulation: Low coefficient of friction, abrasion, moisture, and heat resistant colored polyvinyl chloride (PVC).
Covering: Low coefficient of friction, abrasion, moisture, and heat resistant translucent Nylon polyamide.
Assembly: Cabled assembly with an equipment grounding conductor and a binder tape overall.
Armor: Aluminum Interlocked Armor (AIA).
CONDUCTOR IDENTIFICATION
Three Conductors: Black, Black with Red Stripe, Black with White Stripe
Four Conductors: Black, Black with Red Stripe, Black with Blue Stripe, Black with White Stripe
APPLICATIONS
UL Type MC cables with THHN/THWN-2 conductors are primarily used for services, feeders and branch circuits in commercial and residential applications in accordance with the NEC. Suitable applications include for indoor power and lighting circuits, exposed or concealed, cable tray, raceway (conduit) and embedded in plaster or in contact with masonry. The cable is suitable for dry locations only at temperatures not to exceed 90°C. The cable is rated 600 V.
STANDARDS:
ASTM B800 — 8000 Series Aluminum Alloy Wire for Electrical Purposes – Annealed and Intermediate Tempers
ASTM B801 — Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy for Subsequent Covering or Insulation
UL 83 — Thermoplastic-Insulated Wires and Cables
UL 1479 — Fire Tests of Through-Penetration Firestops
UL 1569 — Metal-Clad Cables.
ICEA S-95-658 / NEMA WC70 — Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
Federal Specification J-C-30B
Armored 5kV/8kv/15kv/35kv 100% or 133% CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket
Armored 5kV 100% or 133% CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket
Voltage: 5kV
Construction
Conductor: Class A or B Compressed concentric stranded copper conductor. Optional water-blocking.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation
Insulation: Extruded, unfilled Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: The metallic shield is flat uncoated 5-mil thick copper tape helically applied with minimum 20% overlap
Ground Wire: Three bare copper ground wires placed at the interstice of the conductor.
Fillers: Non hygroscopic fillers, forming a firm and cylindrical cable core.
Binder Tape: A binder tape is applied to maintain core symmetry and mechanical stability.
Armor: Aluminum Interlocked Armor applied over the binder tape of the cable core
ICEA S-97-682, Utility Shielded Power Cable Rated 5-46 kV
UL-1072 MV-105
UL-1569, Metal Clad Cables
IEEE 383 Flame Test
For 105°C continuous, 140°C emergency, 250°C short-circuit operation.
UL MC-HL available upon request
Armored 8kV 100% or 133% CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket
Voltage: 8kV
Construction
Conductor: Class A or B Compressed concentric stranded copper conductor. Optional water-blocking.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation
Insulation: Extruded, unfilled Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: The metallic shield is flat uncoated 5-mil thick copper tape helically applied with minimum 20% overlap
Ground Wire: Three bare copper ground wires placed at the interstice of the conductor.
Fillers: Non hygroscopic fillers, forming a firm and cylindrical cable core.
Binder Tape: A binder tape is applied to maintain core symmetry and mechanical stability.
Armor: Aluminum Interlocked Armor applied over the binder tape of the cable core
ICEA S-97-682, Utility Shielded Power Cable Rated 5-46 kV
UL-1072 MV-105
UL-1569, Metal Clad Cables
IEEE 383 Flame Test
For 105°C continuous, 140°C emergency, 250°C short-circuit operation.
UL MC-HL available upon request
Armored 15kV 100% or 133% CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket
Voltage: 15kV
Construction
Conductor: Class A or B Compressed concentric stranded copper conductor. Optional water-blocking.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation
Insulation: Extruded, unfilled Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: The metallic shield is flat uncoated 5-mil thick copper tape helically applied with minimum 20% overlap
Ground Wire: Three bare copper ground wires placed at the interstice of the conductor.
Fillers: Non hygroscopic fillers, forming a firm and cylindrical cable core.
Binder Tape: A binder tape is applied to maintain core symmetry and mechanical stability.
Armor: Aluminum Interlocked Armor applied over the binder tape of the cable core
AEIC CS8, Specifications for Shielded Power Cable, 5-46kV
ICEA S-93-639, 5-46 kV Shielded Power Cable
ICEA S-97-682, Utility Shielded Power Cable Rated 5-46 kV
UL-1072 MV-105
UL-1569, Metal Clad Cables
IEEE 383 Flame Test
For 105°C continuous, 140°C emergency, 250°C short-circuit operation.
UL MC-HL available upon request
Armored 25kV 100% or 133% CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket Cable
Voltage: 25kV
Construction
Conductor: Class A or B Compressed concentric stranded copper conductor. Optional water-blocking.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation
Insulation: Extruded, unfilled Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: The metallic shield is flat uncoated 5-mil thick copper tape helically applied with minimum 20% overlap
Ground Wire: Three bare copper ground wires placed at the interstice of the conductor.
Fillers: Non hygroscopic fillers, forming a firm and cylindrical cable core.
Binder Tape: A binder tape is applied to maintain core symmetry and mechanical stability.
Armor: Aluminum Interlocked Armor applied over the binder tape of the cable core
AEIC CS8, Specifications for Shielded Power Cable, 5-46kV
ICEA S-93-639, 5-46 kV Shielded Power Cable
ICEA S-97-682, Utility Shielded Power Cable Rated 5-46 kV
UL-1072 MV-105
UL-1569, Metal Clad Cables
IEEE 383 Flame Test
For 105°C continuous, 140°C emergency, 250°C short-circuit operation.
UL MC-HL available upon request
Armored 35kV CU 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket Cable
Voltage: 35kV
Construction
Conductor: Class A or B Compressed concentric stranded copper conductor. Optional water-blocking.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation
Insulation: Extruded, unfilled Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: The metallic shield is flat uncoated 5-mil thick copper tape helically applied with minimum 20% overlap
Ground Wire: Three bare copper ground wires placed at the interstice of the conductor.
Fillers: Non hygroscopic fillers, forming a firm and cylindrical cable core.
Binder Tape: A binder tape is applied to maintain core symmetry and mechanical stability.
Armor: Aluminum Interlocked Armor applied over the binder tape of the cable core